Type | Supply voltage | Operating modes | Terminal block | Input type | Control output | Time range | Order code |
Multi-range, multi-mode standard timer | 24 to 240 VAC/DC | A2 : ON Delay (Power ON Delay) B3 : Flicker OFF Start (Power ON Start) B4 : Flicker ON Start (Power ON Start) D : Signal OFF Delay E2 : Interval (Power ON Start) E3 : Signal OFF Interval F2 : Cumulative (ON Delay) F3 : Cumulative (Interval) | 10 terminals | Voltage input | Relay, DPDT | 0.1 s to 1,200 h | H3DT-N2 |
8 terminals | Relay, SPDT | H3DT-N1 |
Multi-range, multi-mode expansion timer | A : ON Delay (Signal ON Delay) B : Flicker OFF Start (Signal Start) B2 : Flicker ON Start (Signal Start) C : Signal ON/OFF Delay E : Interval (Signal Start) G : Signal ON/OFF Delay J : One-shot Output (Signal Start) J2 : One-shot Output (Power ON Start) | 10 terminals | Relay, DPDT | H3DT-L2 |
8 terminals | Relay, SPDT | H3DT-L1 |
Power ON-delay timer | 24 to 240 VAC/DC | Power ON-delay | 8 terminals | - | Relay, DPDT | 0.1 s to 1,200 h | H3DT-A2 |
6 terminals | Relay, SPDT | H3DT-A1 |
Twin timer | 24 to 240 VAC/DC | Flicker OFF start/flicker ON start | 6 terminals | - | Relay, SPDT | 0.1 s to 1,200 h | H3DT-F |
Star-delta timer | 24 to 240 VAC/DC | Time-limit operation/self-resetting | 8 terminals | - | Relay, Time-limit Star circuit, SPDT Delta circuit, SPDT | 1 to 120 s | H3DT-G |
Power OFF-delay Timer | 100 to 120 VAC | Instantaneous operation/time-limit reset | 6 terminals | - | Relay, SPDT | 0.1 to 12 s | H3DT-HCS |
200 to 240 VAC | H3DT-HDS |
24 to 48 VAC/DC | H3DT-HBS |
100 to 120 VAC | 1 to 120 s | H3DT-HCL |
200 to 240 VAC | H3DT-HDL |
24 to 48 VAC/DC | H3DT-HBL |
| H3DT |
-N2/-L2 | -N1/-L1 | -A2 | -A1 | -F | -G | -HCS | -HCL | -HDS | -HDL | -HBS/-HBL |
Power supply voltage | 24 to 240 VAC/DC, 50/60 Hz , | 100 to 120 VAC, 50/60 Hz | 200 to 240 VAC, 50/60 Hz | 24 to 48 VAC/DC, 50/60 Hz2 |
Allowable voltage fluctuation range | 85% to 110% of rated voltage |
Power reset | Minimum power-OFF time: 0.1 s | - |
Reset voltage | 10% of rated voltage | - |
Voltage input | 24 to 240 VAC/DC High level: 20.4 to 264 VAC/DC, Low level: 0 to 2.4 VAC/DC | - |
Power consumption | At 240 VAC: 2.3 VA max., at 240 VDC: 1.0 W max., at 24 VDC: 0.3 W max. | At 240 VAC: 2.0 VA max., at 240 VDC: 0.9 W max., at 24 VDC: 0.3 W max.3 | At 240 VAC: 2.2 VA max., at 240 VDC: 0.7 W max., at 24 VDC: 0.3 W max.3 | At 240 VAC: 1.8 VA max., at 240 VDC: 0.6 W max., at 24 VDC: 0.3 W max.3 | At 240 VAC: 1.9 VA max., at 240 VDC: 0.6 W max., at 24 VDC: 0.3 W max. | At 120 VAC: 8.7 VA max. | At 120 VAC: 8.8 VA max. | At 240 VAC: 21.6 VA max. | At 240 VAC: 21.7 VA max. | At 48 VAC: 1.0 VA max., at 24 VDC: 0.4 W max. |
Control output | Contact output: - 5 A at 250 VAC with resistive load (cosφ = 1),
- 5 A at 30 VDC with resistive load,
- 0.15 A max. at 125 VDC with resistive load,
- 0.1A max. at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference value). Contact materials: Ag-alloy (Recommended fuse: BLN5 (Littelfuse) or 0216005MXEP) |
Ambient temperature | Operating: -20 to 60°C (with no icing) Storage: -40 to 70°C (with no icing) |
Accuracy of operating time | ±1% of FS max. (±1% ±10 ms max. at 1.2 s range) | ±1% of FS max. | ±1% of FS max. (±1% ±10 ms max. at 1.2 s range) |
Setting error | ±10% of FS ±0.05 s max. |
Influence of voltage | ±0.5% of FS max. (±0.5% ±10 ms max. at 1.2 s range) | ±0.5% of FS max. | ±0.5% of FS max. (±0.5% ±10 ms max. at 1.2 s range) |
Influence of temperature | ±2% of FS max. (±2% ±10 ms max. at 1.2 s range) | ±2% of FS max. | ±2% of FS max. (±2% ±10 ms max. at 1.2 s range) |
Life expectancy | Mechanical: 10 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) |
Degree of protection | IP30 (Terminal block: IP20) |
Size in mm (H × W × D) | 100×17.5×90 |