Power rating | 30 W | 60 W |
Rated output voltage | 5 V | 12 V | 24 V |
Indication monitor | None | None | None |
Efficiency | 115 VAC input | 78% typ. | 85% typ. | 85% typ. |
230 VAC input | 77% typ. | 86% typ. | 86% typ. |
Input conditions | Voltage range | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second) |
Frequency | 50/60 Hz (47 to 450 Hz) |
Input current | 115 VAC input | 0.53 A typ. | 0.99 A typ. | 1.1 A typ. |
230 VAC input | 0.32 A typ. | 0.61 A typ. | 0.67 A typ. |
Power factor | − |
Leakage current | 115 VAC input | 0.5 mA max. |
230 VAC input | 1 mA max. |
Inrush current | 115 VAC input | 16 A typ. |
230 VAC input | 32 A typ. |
Output characteristics | Rated output current | 5 A | 4.5 A | 2.5 A |
Rated output power | 25 W | 54 W | 60 W |
Maximum boost current | 6 A | 5.4 A | 3 A |
Voltage adjustment range | 4.5 to 5.8V (with V. ADJ) | 10.8 to 14 V (with V. ADJ) | 21.6 to 28 V (with V. ADJ) |
Ripple noise voltage | 100 to 240 VAC input | 130 mVp-p max. at 20 MHz of bandwidth | 120 mVp-p max. at 20 MHz of bandwidth | 110 mVp-p max. at 20 MHz of bandwidth |
Input variation influence | 0.5% max. |
Load variation influence | 1.5% max. |
Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
Start up time | 115 VAC input | 1000 ms max. | 1000 ms max. | 1000 ms max. |
230 VAC input | 1000 ms max. | 1000 ms max. | 1000 ms max. |
Hold time | 115 VAC input | 45 ms typ. | 20 ms typ. | 20 ms typ. |
230 VAC input | 240 ms typ. | 120 ms typ. | 110 ms typ. |
Additional functions | Overload protection | Yes, automatic reset, intermittent operation type. |
Overvoltage protection | Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again). |
Series operation | Yes (For up to two Power Supplies; external diodes required.) |
Parallel operation | Yes (For up to two Power Supplies). |
Output indicator | Yes (LED: Green) |
Alarm indicator | Yes (LED: Red) |
Indication monitor | Measurement and display details | Refer to datasheet. |
Main display | None |
Ethernet communication | Measurement and display details | Refer to datasheet. |
Communication protocol | EtherNet/IP, Modbus TCP |
Physical layer | 100BASE-TX |
Communication specifications | Refer to datasheet. |
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), current cutoff 20 mA |
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA |
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA |
0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA |
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC |
Environment | Ambient operating temperature | −40 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
Storage temperature | −40 to 85°C (with no condensation or icing) |
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) |
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions |
Reliability | MTBF | 160,000 hrs typ. |
Life expectancy | 10 years min. |
Construction | Weight | 250 g max. | 250 g max. | 250 g max. |
Cooling fan | No |
Degree of protection | IP20 by EN/IEC 60529 |
Power rating | 90 W | 120 W |
Rated output voltage | 24 V | 24 V |
Indication monitor | Included | None | Included | None |
Efficiency | 115 VAC input | 86% typ. | 87% typ. | 90% typ. | 90% typ. |
230 VAC input | 87% typ. | 88% typ. | 92% typ. | 92% typ. |
Input conditions | Voltage range | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second) |
Frequency | 50/60 Hz (47 to 450 Hz) | 50/60 Hz (47 to 63 Hz) |
Input current | 115 VAC input | 1.7 A typ. | 1.7 A typ. | 1.2 A typ. | 1.2 A typ. |
230 VAC input | 1.0 A typ. | 1.0 A typ. | 0.63 A typ. | 0.63 A typ. |
Power factor | − | 0.9 min. |
Leakage current | 115 VAC input | 0.5 mA max. |
230 VAC input | 1 mA max. |
Inrush current | 115 VAC input | 16 A typ. |
230 VAC input | 32 A typ. |
Output characteristics | Rated output current | 3.75 A | 5 A |
Rated output power | 90 W | 120 W |
Maximum boost current | − | 6 A |
Voltage adjustment range | 23.0 to 24.1 V | 21.6 to 28 V (with V. ADJ) |
Ripple noise voltage | 100 to 240 VAC input | 300 mVp-p max. at 20 MHz of bandwidth | 150 mVp-p max. at 20 MHz of bandwidth |
Input variation influence | 0.5% max. |
Load variation influence | 1.5% max. |
Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
Start up time | 115 VAC input | 1000 ms max. | 1000 ms max. |
230 VAC input | 1000 ms max. | 1000 ms max. |
Hold time | 115 VAC input | 25 ms typ. | 35 ms typ. |
230 VAC input | 130 ms typ. | 35 ms typ. |
Additional functions | Overload protection | Yes, automatic reset, intermittent operation type. |
Overvoltage protection | Yes, 110% or higher of rated output voltage (90 W), 130% or higher of rated output voltage (120 W), power shut off (shut off the input voltage and turn on the input again. |
Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
Parallel operation | Yes (For up to two Power Supplies). |
Output indicator | Yes (LED: Green) |
Alarm indicator | Yes (LED: Red) |
Indication monitor | Measurement and display details | Refer to datasheet. |
Main display | 7-segment LED (White) | None | 7-segment LED (White) | None |
Ethernet communication | Measurement and display details | Refer to datasheet. |
Communication protocol | EtherNet/IP, Modbus TCP |
Physical layer | 100BASE-TX |
Communication specifications | Refer to datasheet. |
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), current cutoff 20 mA |
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA |
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA |
0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA |
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC |
Environment | Ambient operating temperature | −40 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
Storage temperature | −40 to 85°C (with no condensation or icing) |
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) |
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions |
Reliability | MTBF | 110,000 hrs typ. | 150,000 hrs typ. | 110,000 hrs typ. | 140,000 hrs typ. |
Life expectancy | 10 years min. |
Construction | Weight | 350 g max. | 400 g max. |
Cooling fan | No |
Degree of protection | IP20 by EN/IEC 60529 |
Power rating | 240 W | 480 W |
Rated output voltage | 24 V | 24 V |
Indication monitor | Included | None | Included | None |
Efficiency | 115 VAC input | 91% typ. | 91% typ. | 92% typ. | 92% typ. |
230 VAC input | 93% typ. | 93% typ. | 94% typ. | 94% typ. |
Input conditions | Voltage range | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second) |
Frequency | 50/60 Hz (47 to 63 Hz) | 50/60 Hz (47 to 63 Hz) |
Input current | 115 VAC input | 2.4 A typ. | 2.4 A typ. | 4.6 A typ. | 4.6 A typ. |
230 VAC input | 1.2 A typ. | 1.2 A typ. | 2.3 A typ. | 2.3 A typ. |
Power factor | 0.9 min. |
Leakage current | 115 VAC input | 0.5 mA max. |
230 VAC input | 1 mA max. |
Inrush current | 115 VAC input | 16 A typ. |
230 VAC input | 32 A typ. |
Output characteristics | Rated output current | 10 A | 20 A |
Rated output power | 240 W | 480 W |
Maximum boost current | 15 A | 30 A |
Voltage adjustment range | 21.6 to 28 V (with V. ADJ) |
Ripple noise voltage | 100 to 240 VAC input | 140 mVp-p max. at 20 MHz of bandwidth | 130 mVp-p max. at 20 MHz of bandwidth |
Input variation influence | 0.5% max. |
Load variation influence | 1.5% max. |
Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
Start up time | 115 VAC input | 1000 ms max. | 1000 ms max. |
230 VAC input | 1000 ms max. | 1000 ms max. |
Hold time | 115 VAC input | 35 ms typ. | 25 ms typ. |
230 VAC input | 35 ms typ. | 25 ms typ. |
Additional functions | Overload protection | Yes, automatic reset, intermittent operation type. |
Overvoltage protection | Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again). |
Series operation | Yes (For up to two Power Supplies; external diodes required.) |
Parallel operation | Yes (For up to two Power Supplies) |
Output indicator | Yes (LED: Green) |
Alarm indicator | Yes (LED: Red) |
Indication monitor | Measurement and display details | Refer to datasheet. |
Main display | 7-segment LED (White) | None | 7-segment LED (White) | None |
Ethernet communication | Measurement and display details | Refer to datasheet. |
Communication protocol | EtherNet/IP, Modbus TCP |
Physical layer | 100BASE-TX |
Communication specifications | Refer to datasheet. |
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), |
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA |
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA |
0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA |
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC |
Environment | Ambient operating temperature | −40 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) |
Storage temperature | −40 to 85°C (with no condensation or icing) |
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) |
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions |
Reliability | MTBF | 100,000 hrs typ. | 130,000 hrs typ. | 90,000 hrs typ. | 120,000 hrs typ. |
Life expectancy | 10 years min. |
Construction | Weight | 700 g max. | 1,100 g max. |
Cooling fan | No |
Degree of protection | IP20 by EN/IEC 60529 |
Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
EMI | Conducted emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
Radiated emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
EMS | Conforms to EN 61204-3 high severity levels |
Safety standards | UL 508, ANSI/ISA 12.12.01 (Listing) (For 30 W, 60 W, and 90 W only Class 2 Output: Per UL 1310) CSA C22.2 No. 107.1, CSA C22.2 No. 213 (cUL) (For 30 W, 60 W, and 90 W only Class 2 Output: Per CSA C22.2 No. 223) UL 60950-1, UL 62368-1 (Recognition) OVC II ( ≤ 3000 m) Pol2 (For 30 W, 60 W, and 90 W only LPS) CSA C22.2 No. 60950-1, No. 62368-1 (cUR) OVC II ( ≤ 3000 m) Pol2 (For 30 W, 60 W, and 90 W only LPS) EN 50178 OVC III ( ≤ 2000 m) OVC II (2000 m < and ≤ 3000 m) Pol2 EN 60950-1, EN 62368-1 OVC II ( ≤ 3000 m) Pol2 (For 30 W, 60 W, and 90 W only LPS) EAC (TR CU 004 / 2011, TR CU 020 / 2011) RCM (EN61000-6-4) Korea Radio Waves Act (Law No. 10564) Conforms to PELV (EN/IEC 60204-1) Conforms to EN/IEC 61558-2-16 |
SEMI | Conforms to F47-0706 (200 to 240 VAC input) |