Supply voltage | 24 VDC |
Operating voltage range | 85 to 110% of the rated supply voltage |
Power consumption | 2.5 W max. (at max. DC load with all indicators lit) |
Ambient temperature | Operating: −10 to 55°C (with no condensation or icing) Storage: −25 to 65°C (with no condensation or icing) |
Display refresh period | Sampling period (sampling times multiplied by number of averaging times if average processing is selected) |
Max. displayed digits | 5 digits (−19999 to 99999) |
Display | 7-segment digital display, character height: 7.0 mm |
Polarity display | “-” is displayed automatically with a negative input signal |
Zero display | Leading zeros are not displayed |
Scaling function | Programmable with front-panel key inputs (range of display: -19999 to 99999). The decimal point position can be set as desired. |
External controls | HOLD: (measurement value held) |
ZERO: (forced-zero) |
Hysteresis setting | Programmable with front-panel key inputs (0001 to 9999) |
Other functions | Programmable color display Selectable output operating action Teaching set values Average processing (simple average) Lockout configuration Communications writing control (communications output models only) |
Output | Relays: 2 SPST-NO Transistors: 3 NPN open collector 3 PNP open collector |
Combinations: Communications output (RS-485) + relay outputs Communications output (RS-485) + transistor outputs Communications output (RS-485) + transistor outputs (3 PNP open collector) |
Communications | Communications function: RS-485 |
Delay in comparative outputs (transistor outputs) | 750 ms max. |
Degree of protection | Front-panel: NEMA4X for indoor use (equivalent to IP66) Rear case: IEC standard IP20 Terminals: IEC standard IP20 |
Memory protection | Non-volatile memory (EEPROM) (possible to rewrite 100,000 times) |
Size in mm (H×W×D) | 24×48×80 |