DZ47LE RCBO
DZ47LE Residual Current Operated Circuit Breaker with over-current protection (Electronic)
1. Application
Personnel and fire protection
Cable and line protection against overload and short-circuits
2. General rules for choosing RCBO:
a.Rated residual operating current
I∆n ≤ 30 mA: additional protection in the case of direct contact I∆n ≤300 mA: preventative fire protection in the case of ground fault currents
b.Tripping class
AC class – Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.
c.Tripping curve
C curve (5-10 In) protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current.
D curve (10-14 In) protection and control of the circuits against overloads and short-circuits; protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps).