| Type | Supply voltage | Control output | Time setting range | Operating modes | Order code |
| Screw terminal type | Screw-less clamp type |
| Multi-functional timer | 24 to 230 VAC (50/60 Hz)/ 24 to 48 VDC | SPDT | 0.1 s to120 h | ON-delay, flicker OFF start, flicker ON start, signal ON/OFF-delay, signal OFF-delay, interval, one-shot | H3DS-ML | H3DS-MLC |
| Standard timer | ON-delay, flicker ON start, interval, oneshot | H3DS-SL | H3DS-SLC |
| Single function timer | ON-delay | H3DS-AL | H3DS-ALC |
| Twin timer | Relay SPDT | 0.1 s to 12 h | Flicker OFF start, flicker ON start | H3DS-FL | H3DS-FLC |
| Star-delta timer | 2× Relay SPST-NO | 1 s to 120 s | Star-delta | H3DS-GL | H3DS-GLC |
| Two-wired timer | 24 to 230 VAC/VDC (50/60 Hz) | SCR output | 0.1 s to 120 h | ON-delay | H3DS-XL | H3DS-XLC |
| Terminal block | Screw terminal type: Clamps two 2.5 mm2 max. bar terminals without sleeves Screw-less clamp type: Clamps two 1.5 mm2 max. bar terminals without sleeves |
| Mounting method | DIN-rail mounting |
| Operating voltage range | 85 to 110% of rated supply voltage |
| Power reset | Minimum power-off time: 0.1 s, 0.5 s for H3DS-G |
| Reset voltage | 2.4 VAC/VDC max., 1.0 VAC/VDC max. for H3DS-X |
| Voltage input | Max. permissible capacitance between input lines (terminals B1 and A2): 2,000 pF |
| Load connectable in parallel with inputs (terminals B1 and A1) |
| H-level: 20.4 to 253 VAC/20.4 to 52.8 VDC |
| L-level: 0 to 2.4 VAC/VDC |
| Control output | Contact output: 5 A at 250 VAC with resistive load (cosφ = 1) |
| 5 A at 30 VDC with resistive load (cosφ = 1) |
| Ambient temperature | Operating: -10 to 55°C (with no icing) |
| Storage: -25 to 65°C (with no icing) |
| Accuracy of operating time | ±1% max. of FS (±1% ±10 ms max. at 1.2 s range) |
| Setting error | ±10% ±50 ms max. of FS |
| Influence of voltage | ±0.7% max. of FS (±0.7% ±10 ms max. at 1.2 s range) |
| Influence of temperature | ±5% max. of FS (±5% ±10 ms max. at 1.2 s range) |
| Life expectancy (not H3DS-X) | Mechanical: 10 million operations min. (under no load at 1,800 operations/h) |
| Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) |
| Size in mm(HxWxD) | 80x17.5x73 |