| Power rating | 15 W |
| Item | Output voltage | 5 V | 12 V | 15 V | 24 V |
| Efficiency | 100 VAC input | 80% typ. | 84% typ. | 84% typ. | 85% typ. |
| 200 VAC input | 80% typ. | 84% typ. | 84% typ. | 86% typ. |
| 230 VAC input | 80% typ. | 84% typ. | 84% typ. | 86% typ. |
| Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 370 VDC |
| Frequency | 50/60 Hz (47 to 450 Hz) |
| Current | 100 VAC input | 0.32 A typ. |
| 200 VAC input | 0.2 A typ. |
| Power factor | − |
| Leakage current | 100 VAC input | 0.5 mA max. |
| 200 VAC input | 1 mA max. |
| Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
| 200 VAC input | 28 A typ. |
| Output | Rated Output Current | 3 A | 1.3 A | 1 A | 0.65 A |
| Voltage adjustment range | −10% to 15% (with V.ADJ) |
| Ripple & Noise voltage | 100 to 240 VAC input | 40 mVp-p max. | 40 mVp-p max. | 40 mVp-p max. | 60 mVp-p max. |
| Input variation influence | 0.5% max. |
| Load variation influence | 1.0% max. |
| Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
| Startup time | 100 VAC input | 1,000 ms max. |
| 200 VAC input | 1,000 ms max. |
| Hold time | 100 VAC input | 15 ms typ. | 14 ms typ. | 15 ms typ. | 15 ms typ. |
| 200 VAC input | 75 ms typ. | 70 ms typ. | 75 ms typ. | 70 ms typ. |
| Additional functions | Overload protection | Yes, automatic reset |
| Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
| Overheat protection | No |
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
| Parallel operation | No (However, backup operation is possible, external diodes are required.) |
| Remote sensing | No |
| Remote control | No |
| Output indicator | Yes (LED: Green) |
| Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
| Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
| Storage temperature | −25 to 75°C (with no condensation or icing) |
| Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
| Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
| Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
| Reliability | MTBF | 135,000 hrs min. |
| Life expectancy | 10 years min. |
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| EMS | Conforms to EN 61204-3 high severity levels |
| Safety Standards | UL 508 (Listing, excluding models with connector option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.60950-1 (excluding models with connector option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
| Marine Standards | No |
| SEMI | Conforms to F47-0706 (200 VAC input) |
| Power rating | 30 W |
| Item | Output voltage | 5 V | 12 V | 15 V | 24 V |
| Efficiency | 100 VAC input | 81% typ. | 84% typ. | 86% typ. | 86% typ. |
| 200 VAC input | 81% typ. | 86% typ. | 88% typ. | 88% typ. |
| 230 VAC input | 81% typ. | 86% typ. | 88% typ. | 89% typ. |
| Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 370 VDC |
| Frequency | 50/60 Hz (47 to 450 Hz) |
| Current | 100 VAC input | 0.72 A typ. |
| 200 VAC input | 0.43 A typ. |
| Power factor | − |
| Leakage current | 100 VAC input | 0.5 mA max. |
| 200 VAC input | 1 mA max. |
| Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
| 200 VAC input | 28 A typ. |
| Output | Rated Output Current | 6 A | 3 A | 2.4 A | 1.5 A |
| Voltage adjustment range | −10% to 15% (with V.ADJ) |
| Ripple & Noise voltage | 100 to 240 VAC input | 50 mVp-p max. | 60 mVp-p max. | 50 mVp-p max. | 60 mVp-p max. |
| Input variation influence | 0.5% max. |
| Load variation influence | 1.0% max. |
| Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
| Startup time | 100 VAC input | 1,000 ms max. |
| 200 VAC input | 1,000 ms max. |
| Hold time | 100 VAC input | 11 ms typ. | 10 ms typ. | 11 ms typ. | 10 ms typ. |
| 200 VAC input | 60 ms typ. | 50 ms typ. | 50 ms typ. | 55 ms typ. |
| Additional functions | Overload protection | Yes, automatic reset |
| Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
| Overheat protection | No |
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
| Parallel operation | No (However, backup operation is possible, external diodes are required.) |
| Remote sensing | No |
| Remote control | No |
| Output indicator | Yes (LED: Green) |
| Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
| Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
| Storage temperature | −25 to 75°C (with no condensation or icing) |
| Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
| Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
| Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
| Reliability | MTBF | 135,000 hrs min. |
| Life expectancy | 10 years min. |
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| EMS | Conforms to EN 61204-3 high severity levels |
| Safety Standards | UL 508 (Listing, excluding models with connector option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.60950-1 (excluding models with connector option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
| Marine Standards | No |
| SEMI | Conforms to F47-0706 (200 VAC input) |
| Power rating | 50 W |
| Item | Output voltage | 5 V | 12 V | 15 V | 24 V |
| Efficiency | 100 VAC input | 81% typ. | 84% typ. | 86% typ. | 86% typ. |
| 200 VAC input | 82% typ. | 86% typ. | 88% typ. | 89% typ. |
| 230 VAC input | 82% typ. | 86% typ. | 88% typ. | 89% typ. |
| Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 370 VDC |
| Frequency | 50/60 Hz (47 to 450 Hz) |
| Current | 100 VAC input | 1.1 A typ. |
| 200 VAC input | 0.62 A typ. |
| Power factor | − |
| Leakage current | 100 VAC input | 0.5 mA max. |
| 200 VAC input | 1 mA max. |
| Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
| 200 VAC input | 28 A typ. |
| Output | Rated Output Current | 8 A | 4.3 A | 3.5 A | 2.2A |
| Voltage adjustment range | −10% to 15% (with V.ADJ) | | | |
| Ripple & Noise voltage | 100 to 240 VAC input | 40 mVp-p max. | 40 mVp-p max. | 40 mVp-p max. | 60 mVp-p max. |
| Input variation influence | 0.5% max. |
| Load variation influence | 1.0% max. |
| Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
| Startup time | 100 VAC input | 1,000 ms max. |
| 200 VAC input | 1,000 ms max. |
| Hold time | 100 VAC input | 14 ms typ. | 11 ms typ. | 10 ms typ. | 10 ms typ. |
| 200 VAC input | 75 ms typ. | 60 ms typ. | 60 ms typ. | 55 ms typ. |
| Additional functions | Overload protection | Yes, automatic reset |
| Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
| Overheat protection | No |
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
| Parallel operation | No (However, backup operation is possible, external diodes are required.) |
| Remote sensing | No |
| Remote control | No |
| Output indicator | Yes (LED: Green) |
| Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
| 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
| Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
| Storage temperature | −25 to 75°C (with no condensation or icing) |
| Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
| Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
| Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
| Reliability | MTBF | 135,000 hrs min. |
| Life expectancy | 10 years min. |
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| EMS | Conforms to EN 61204-3 high severity levels |
| Safety Standards | UL 508 (Listing, excluding models with connector option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.60950-1 (excluding models with connector option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
| Marine Standards | No |
| SEMI | Conforms to F47-0706 (200 VAC input) |
| Power rating | 100 W |
| Item | Output voltage | 5 V | 12 V | 15 V | 24 V |
| Efficiency | 100 VAC input | 79% typ. | 84% typ. | 85% typ. | 87% typ. |
| 200 VAC input | 81% typ. | 86% typ. | 87% typ. | 89% typ. |
| 230 VAC input | 81% typ. | 86% typ. | 87% typ. | 89% typ. |
| Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 370 VDC |
| Frequency | 50/60 Hz (47 to 450 Hz) |
| Current | 100 VAC input | 2.1 A typ. |
| 200 VAC input | 1.2 A typ. |
| Power factor | − |
| Leakage current | 100 VAC input | 0.5 mA max. |
| 200 VAC input | 1 mA max. |
| Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
| 200 VAC input | 28 A typ. |
| Output | Rated Output Current | 16 A | 8.5 A | 7 A | 4.5 A |
| Voltage adjustment range | −10% to 15% (with V.ADJ) |
| Ripple & Noise voltage | 100 to 240 VAC input | 70 mVp-p max. | 90 mVp-p max. | 100 mVp-p max. | 80 mVp-p max. |
| Input variation influence | 0.5% max. |
| Load variation influence | 1.0% max. |
| Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
| Startup time | 100 VAC input | 1,000 ms max. |
| 200 VAC input | 1,000 ms max. |
| Hold time | 100 VAC input | 12 ms typ. 11 ms typ. 11 ms typ. 10 ms typ. |
| 200 VAC input | 70 ms typ. | 55 ms typ. | 55 ms typ. | 55 ms typ. |
| Additional functions | Overload protection | Yes, automatic reset |
| Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
| Overheat protection | No |
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
| Parallel operation | No (However, backup operation is possible, external diodes are required.) |
| Remote sensing | No |
| Remote control | Yes (Only for models with remote control option) |
| Output indicator | Yes (LED: Green) |
| Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
| Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
| Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
| Storage temperature | −25 to 75°C (with no condensation or icing) |
| Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
| Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
| Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
| Reliability | MTBF | 135,000 hrs min. |
| Life expectancy | 10 years min. |
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| EMS | Conforms to EN 61204-3 high severity levels |
| Safety Standards | UL 508 (Listing, excluding models with connector option or remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option or remote control option) CSA C22.2 No.60950-1 (excluding models with connector option or remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
| Marine Standards | No |
| SEMI | Conforms to F47-0706 (200 VAC input) |
| Power rating | 150 W |
| Item | Output voltage | 5 V | 12 V | 15 V | 24 V | 48 V |
| Efficiency | 100 VAC input | 78% typ. | 84% typ. | 85% typ. | 87% typ. | 85% typ. |
| 200 VAC input | 81% typ. | 87% typ. | 88% typ. | 89% typ. | 88% typ. |
| 230 VAC input | 81% typ. | 87% typ. | 88% typ. | 90% typ. | 88% typ. |
| Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 370 VDC |
| Frequency | 50 /60 Hz (47 to 450 Hz) |
| Current | 100 VAC input | 3 A typ. |
| 200 VAC input | 1.8 A typ. |
| Power factor | − |
| Leakage current | 100 VAC input | 0.5 mA max. |
| 200 VAC input | 1 mA max. |
| Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
| 200 VAC input | 28 A typ. |
| Output | Rated Output Current | 21 A | 13 A | 10 A | 6.5 A | 3.3 A |
| Voltage adjustment range | −10% to 15% (with V.ADJ) |
| Ripple & Noise voltage | 100 to 240 VAC input | 100 mVp-p max. | 110 mVp-p max. | 80 mVp-p max. | 110 mVp-p max. | 120 mVp-p max. |
| Input variation influence | 0.5% max. |
| Load variation influence | 1.0% max. |
| Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
| Startup time | 100 VAC input | 1,000 ms max. |
| 200 VAC input | 1,000 ms max. |
| Hold time | 100 VAC input | 14 ms typ. | 10 ms typ. | 10 ms typ. | 10 ms typ. | 11 ms typ. |
| 200 VAC input | 80 ms typ. | 55 ms typ. | 55 ms typ. | 55 ms typ. | 55 ms typ. |
| Additional functions | Overload protection | Yes, automatic reset |
| Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
| Overheat protection | No |
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
| Parallel operation | No (However, backup operation is possible, external diodes are required.) |
| Remote sensing | No |
| Remote control | Yes (Only for models with remote control option) |
| Output indicator | Yes (LED: Green) |
| Insulation | Withstand voltage | 3 kVAC for 1 min.(between all input terminals and output terminals) current cutoff 20 mA |
| 2 kVAC for 1 min.(between all input terminals and PE terminals) current cutoff 20 mA |
| 1 kVAC for 1 min.(between all output terminals and PE terminals) current cutoff 20 mA |
| Only Remote control 500 VAC for 1 min.(between all output terminals and RC terminals) current cutoff 20 mA |
| Insulation resistance | 100 MΩ min.(between all output terminals and all input terminals/PE terminals) at 500 VDC |
| Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
| Storage temperature | −25 to 75°C (with no condensation or icing) |
| Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
| Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
| Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
| Reliability | MTBF | 135,000 hrs min. |
| Life expectancy | 10 years min. |
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 (Applicable at 80% or less of the rated load.) |
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| EMS | Conforms to EN 61204-3 high severity levels |
| Safety Standards | UL 508 (Listing, excluding models with connector option or remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option or remote control option) CSA C22.2 No.60950-1 (excluding models with connector option or remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
| Marine Standards | No |
| SEMI | Conforms to F47-0706 (200 VAC input) |
| Power rating | 300 W |
| Item | Output voltage | 12 V | 15 V | 24 V | 48 V |
| Efficiency | 100 VAC input | 81% typ. | 81% typ. | 82% typ. | 82% typ. |
| 200 VAC input | 85% typ. | 85% typ. | 87% typ. | 87% typ. |
| 230 VAC input | 85% typ. | 86% typ. | 87% typ. | 87% typ. |
| Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 370 VDC |
| Frequency | 50/60 Hz (47 to 63 Hz) |
| Current | 100 VAC input | 4.2 A typ. |
| 200 VAC input | 2.1 A typ. |
| Power factor | 0.9 min. |
| Leakage current | 100 VAC input | 0.5 mA max. |
| 200 VAC input | 1 mA max. |
| Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
| 200 VAC input | 28 A typ. |
| Output | Rated Output Current | 25 A | 20 A | 14 A | 7 A |
| Voltage adjustment range | −10% to 15% (with V.ADJ) |
| Ripple & Noise voltage | 100 to 240 VAC input | 140 mVp-p max. | 270 mVp-p max. | 150 mVp-p max. | 330 mVp-p max. |
| Input variation influence | 0.5% max. |
| Load variation influence | 1.0% max. |
| Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
| Startup time | 100 VAC input | 1,000 ms max. |
| 200 VAC input | 1,000 ms max. |
| Hold time | 100 VAC input | 30 ms typ. | 30 ms typ. | 30 ms typ. | 30 ms typ. |
| 200 VAC input | 30 ms typ. | 25 ms typ. | 30 ms typ. | 30 ms typ. |
| Additional functions | Overload protection | Yes, automatic reset |
| Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
| Overheat protection | Yes, power shut off (shut off the input voltage and turn on the input again) |
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
| Parallel operation | No (However, backup operation is possible, external diodes are required.) |
| Remote sensing | No |
| Remote control | Yes (Only for models with remote control option) |
| Output indicator | Yes (LED: Green) |
| Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
| Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
| Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
| Storage temperature | −25 to 75°C (with no condensation or icing) |
| Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
| Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
| Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
| Reliability | MTBF | 135,000 hrs min. |
| Life expectancy | 10 years min. |
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| EMS | Conforms to EN 61204-3 high severity levels |
| Safety Standards | UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with remote control option) CSA C22.2 No.60950-1 (excluding models with remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
| Marine Standards | No |
| SEMI | Conforms to F47-0706 (200 VAC input) |
| Power rating | 600 W |
| Item | Output voltage | 12 V | 15 V | 24 V | 48 V |
| Efficiency | 100 VAC input | 84% typ. | 84% typ. | 85% typ. | 88% typ. |
| 200 VAC input | 88% typ. | 88% typ. | 89% typ. | 92% typ. |
| 230 VAC input | 88% typ. | 88% typ. | 90% typ. | 92% typ. |
| Input | Voltage range | Single phase, 85 to 264 VAC, 120 to 350 VDC |
| Frequency | 50/60 Hz (47 to 63 Hz) |
| Current | 100 VAC input | 7.7 A typ. |
| 200 VAC input | 3.8 A typ. |
| Power factor | 0.9 min. |
| Leakage current | 100 VAC input | 0.5 mA max. |
| 200 VAC input | 1 mA max. |
| Inrush current (for a cold start at 25°C) | 100 VAC input | 14 A typ. |
| 200 VAC input | 28 A typ. |
| Output | Rated Output Current | 50 A | 40 A | 27 A | 13 A |
| Voltage adjustment range | −10% to 15% (with V.ADJ) |
| Ripple & Noise voltage | 100 to 240 VAC input | 170 mVp-p max. | 170 mVp-p max. | 280 mVp-p max. | 340 mVp-p max. |
| Input variation influence | 0.5% max. |
| Load variation influence | 1.0% max. |
| Temperature variation influence | 100 to 240 VAC input | 0.05%/°C max. |
| Startup time | 100 VAC input | 1,000 ms max. |
| 200 VAC input | 1,000 ms max. |
| Hold time | 100 VAC input | 30 ms typ. | 25 ms typ. | 30 ms typ. | 30 ms typ. |
| 200 VAC input | 30 ms typ. | 25 ms typ. | 30 ms typ. | 30 ms typ. |
| Additional functions | Overload protection | Yes, automatic reset |
| Overvoltage protection | Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) |
| Overheat protection | Yes, power shut off (shut off the input voltage and turn on the input again) |
| Series operation | Yes (For up to two Power Supplies, external diodes are required.) |
| Parallel operation | Yes (up to five Power Supplies, S8FS-G60024 (models with parallel operation option) only). |
| Remote sensing | No |
| Remote control | Yes (Only Remote control) |
| Output indicator | Yes (LED: Green) |
| Insulation | Withstand voltage | 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA |
| 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA |
| 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA |
| Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA |
| Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
| Environment | Ambient operating temperature | −20 to 70°C (with no condensation or icing) |
| Storage temperature | −25 to 75°C (with no condensation or icing) |
| Ambient operating humidity | 90% max. (Storage humidity: 90% max.) |
| Vibration resistance | 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions |
| Shock resistance | 150 m/s², 3 times each in ±X, ±Y, ±Z directions |
| Reliability | MTBF | 135,000 hrs min. |
| Life expectancy | 10 years min. |
| Standards | Harmonic current emissions | Conforms to EN 61000-3-2 |
| EMI | Conducted Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| Radiated Emissions | Conforms to EN 61204-3 Class B, EN 55011 Class B |
| EMS | Conforms to EN 61204-3 high severity levels |
| Safety Standards | UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with remote control option) CSA C22.2 No.60950-1 (excluding models with remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN 60950-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16. |
| Marine Standards | No |
| SEMI | Conforms to F47-0706 (200 VAC input) |